What does EIFS stand for?
EIFS (pronounced eefs) is an acronym for Exterior Insulation and Finish System. An EIFS consists of five basic components:
- Insulation board, made of polystyrene or polyisocyanurate foam
- A specially formulated adhesive and/or mechanical attachment of the insulation to a substrate
- Glass fiber reinforcing mesh
- A durable, water-resistant base coat, which is applied on top of the insulation that functions as the weather barrier
- An attractive and durable finish coat - typically using acrylic co-polymer technology- which is both colorfast and crack-resistant
|
| » |
What is the difference between PM and PB EIFS?
"PM" refers to Polymer Modified and "PB" refers to Polymer Based. Class PB EIFS typically use adhesively fastened expanded polystyrene (EPS) insulation, and glass fiber reinforcing mesh embedded in a nominal 1/16 inch (1.6mm) base coat. PB EIFS can incorporate additional layers of base coat and reinforcing mesh to achieve higher impact resistance. An EIFS finish coat is used over the base coat. PB EIFS represents the majority of EIFS used in North America.
|
| » |
What is the maximum thickness allowed for foam shapes to achieve architectural treatments such as accent bands and cornices?
The national model building codes generally limit foam thickness to a 4-inch maximum. However, precedence exists for using thicker expanded polystyrene foam insulation when acceptable to local authorities having jurisdiction.
|
| » |
Can coatings be applied directly to Dens-Glass Gold?
Coatings can be directly applied to a sheltered soffit area. Direct application to Dens-Glass Gold as a primary wall cladding is not approved other than for specific.
|
| » |
Does EIFS require an expansion joint at all floor lines?
At wood framed buildings only. Unless there is a Web Truss floor joist, wood I-beam Truss-joist type, or Laminated Veneer Lumber floor joist, then there is no expansion joint needed.
|
| » |
What is the minimum space required for expansion joints?
A minimum gap of 3/4" for expansion joints unless otherwise specified by the architect.
|
| » |
What maintenance do wall systems require?
Periodic cleaning is suggested. Sealants should be reviewed every year or so. All cladding systems, including brick and vinyl, require some maintenance.
|
| » |
When should I maintain the system?
Take a visual inspection every six months, when you are doing your Spring and Fall cleanup. Look for cracks, bulges, stains, gouges, penetrations, vandalism, etc. Repair any damage or deficiencies.
|
| » |
How do I clean the finish coat?
Basically, you can use mild cleaning detergents, and low water pressure "300/500 PSI", cool water, and a soft bristle brush. Do not use the following: any cleaner that is solvent based; high water pressure; hot water; or wire brushes.
|
| » |
How do I paint my wall system?
For situations where you might wish to change the color of the building, or paint the building for some other reason, EIFS manufactures several quality paint products to re-coat and enhance the existing coating. Other alternatives are to use a quality high grade 100% acrylic exterior grade paint.
|
| » |
Who do I contact if I need repairs?
Call Exterior Designs, Inc.
|
| » |
How do I get graffiti off my walls?
The best way is to repaint the area.
|
| » |
How long should this product last?
If properly maintained, the cladding will last a long time. The first EIFS walls in the US were installed in 1969; most are still in service. EIFS was first used after WWII in Europe. Today it is a large part of their exterior cladding market.
|
| » |
What is the maximum deflection criteria for the EIFS PB Wall System?
L/240.
|
| » |
When are expansion joints required for installation with the EIFS Wall System?
Expansion joints are required where there are changes in substrate, at floor lines in typical wood framed construction, and where movement is anticipated in the wall assembly and where expansion joints exist in the substrate.
|
| » |
Can the EIFS finish be installed directly to wood?
No.
|
| » |
Can the finish be installed to metal, such as a sign?
No.
|
| » |
How wide should expansion joints be when installed with the EIFS Wall System?
This is an issue that is the responsibility of the design professional.
|
| » |
What determines the use and location of a vapor retarder in a wall assembly?
The selection and/or location of a vapor retarder is project specific based on numerous factors including climate, wall components, etc., and as such is a design consideration that is the responsibility of the design professional.
|
| » |
If EPS insulation board stays in the sun for a long period of time and yellowing occurs what should be done?
The EPS insulation board should be rasped down until the yellowing is removed. Make sure that there is at least 3/4" of insulation board remaining after the rasping is done.
|
| » |
What kind of sealant do EIFS manufacturer's recommend?
EIFS manufacturer's recommend an ultra-low modulus sealant that is capable of 100% elongation and 50% compression.
|
| » |
What is back wrapping?
Back wrapping is the traditional method of encapsulating the insulation board edge. Back wrapping simply means that the insulation board is wrapped in fabric reinforced base coat at edges at terminations and that the mesh extends behind the insulation board at least 21/2". Edge wrapping means that mesh reinforced base coat extends over the edges of insulation at terminations and onto the framing or masonry.
|
| » |
What is Vinyl Track used for?
Vinyl Track is used in many locations as an alternative to back wrapping. Although it cannot be used in every situation, it provides a convenient alternative to back wrapping, and is a time saving accessory to applicators.
|
| » |
How high should the EIF system be terminated above grade, pavement and rooflines?
The EIF system should be terminated above pavement and above rooflines a minimum of 2 inches. The system should be terminated a minimum of 6 inches above grade at un-paved areas.
|
| » |
Can a "V" groove reveal be considered a control joint?
A "V" groove reveal cannot be considered a control joint since a true joint is a "built-in" break in the system where cracking is anticipated.
|